It might be time-consuming and tired to prepare for the CFI-I exam without a specialist study material. So it's would be the best decision to choose our CFI-I study tool as your learning partner. Our CFI-I study tool also gives numerous candidates a better perspective on the real exam. Having been specializing in the research of CFI-I Latest Practice Materials, we now process a numerous of customers with our endless efforts, and we believe that our CFI-I exam guide will percolate to your satisfaction.
| Topic | Details |
|---|---|
| Topic 1 |
|
| Topic 2 |
|
| Topic 3 |
|
| Topic 4 |
|
>> Valid NFPA CFI-I Exam Objectives <<
The reason behind our confidence is the hard work of our professionals. We have hired a team who analyze past papers, NFPA Certified Fire Inspector I (CFI-1) Exam examination syllabus and add the most probable NFPA CFI-I exam questions in three easy-to-use formats. These formats include CFI-I Pdf Dumps file, web-based Certified Fire Inspector I (CFI-1) practice test, and desktop practice exam software. Keep reading to find the specifications of our CFI-I exam practice material's three formats.
NEW QUESTION # 99
Underground and exposed piping shall be flow tested to determine the internal condition of the piping at what minimal interval?
Answer: B
Explanation:
Comprehensive and Detailed Step-by-Step Explanation:
Flow Testing for Piping:
According to NFPA 25 (Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems), Section 14.2.1, underground and exposed piping must be flow tested at least once every 5 years.
This ensures the internal condition of the piping is adequate and free from obstructions, corrosion, or deposits that could affect water flow.
Why Every 5 Years is Required:
Over time, buildup or deterioration within the piping can restrict water flow, impacting the performance of the fire protection system.
Regular testing helps identify and address issues before they compromise fire safety.
Other Options Explained:
Option B (Every 6 years), Option C (Every 10 years), Option D (Every 20 years): These intervals do not meet the minimum requirements established in NFPA 25.
Summary:
Flow testing of underground and exposed piping must be conducted once every 5 years to ensure their internal condition meets fire protection standards.
NEW QUESTION # 100
Which one of the following is a primary reason for issuing a permit?
Answer: B
Explanation:
Comprehensive and Detailed Step-by-Step Explanation:
Purpose of Permits:
Permits are issued primarily to ensure the jurisdiction (Authority Having Jurisdiction - AHJ) is aware of potentially hazardous situations or conditions and can enforce compliance with fire and safety codes.
Permits also provide an opportunity to inspect operations, processes, or structures to ensure safety.
NFPA References:
According to NFPA 1 (Fire Code), permits are required for activities that could pose risks, such as hazardous materials, fire protection system installations, and occupancy changes.
Other Options Explained:
Option A (To meet fire insurance requirements): Permits are not issued for insurance purposes, although compliance may indirectly affect insurance.
Option C (Less restrictive code requirements): Permits are not for bypassing codes.
Option D (Economic feasibility): Economic factors are unrelated to the permitting process.
Summary:
Permits are issued to make the jurisdiction aware of potentially hazardous situations or conditions and ensure compliance with fire safety regulations.
NEW QUESTION # 101
When submitting materials for plan review, the applicant has the responsibility to ensure I . That construction documents include all of the fire protection requirements.
II . That shop drawings are correct and in compliance with applicable codes and standards.
III . That all contracts are in place.
Answer: D
Explanation:
Comprehensive and Detailed Step-by-Step Explanation:
Responsibilities for Plan Review:
Per NFPA 1 (Fire Code), Chapter 1, and general fire code principles, the applicant must ensure:
I: Construction documents include all fire protection requirements.
II: Shop drawings are accurate and comply with relevant codes (e.g., NFPA 13, NFPA 72).
Why Contracts Are Not Required:
Contracts (III) are not within the purview of plan review and AHJ approval. They are part of business agreements, not technical compliance.
Other Options Explained:
Option C (II and III): Incorrect as contracts (III) are irrelevant to plan review.
Option D (I, II, and III): Incorrect for the same reason.
Summary:
The applicant must ensure that construction documents and shop drawings comply with all fire protection requirements.
NEW QUESTION # 102
What is the acceptable flow of water normally required for a pipe schedule sprinkler system that has a minimum pressure of 20 psi (14 bar) in an ordinary hazard occupancy?
Answer: D
Explanation:
Comprehensive and Detailed Step-by-Step Explanation:
Pipe Schedule Sprinkler Systems:
According to NFPA 13 (Standard for the Installation of Sprinkler Systems), Table 11.2.3.2.1, the required flow rate for ordinary hazard occupancies is typically 850-1,500 gpm (3,218-5,678 L/min) at a minimum pressure of 20 psi (14 bar).
Ordinary Hazard Occupancies:
These include areas with moderate fire loads, such as manufacturing spaces or storage areas, where a higher water flow is required compared to light hazard occupancies.
Other Options Explained:
Option A (500-750 gpm): Insufficient for ordinary hazard occupancies; more suited to light hazard classifications.
Option B (700-1,000 gpm): Too low for larger or higher-risk ordinary hazard areas.
Option D (1,750-2,000 gpm): Exceeds the typical requirement for ordinary hazards.
Summary:
The acceptable flow for a pipe schedule sprinkler system in an ordinary hazard occupancy is 850-1,500 gpm (3,218-5,678 L/min) at 20 psI .
NEW QUESTION # 103
A fully sprinklered structure containing 1,500 sprinklers requires a minimum supply of how many spare sprinklers?
Answer: D
Explanation:
Comprehensive and Detailed Step-by-Step Explanation:
Spare Sprinkler Requirements:
According to NFPA 13 (Standard for the Installation of Sprinkler Systems), Section 6.2.9, the required number of spare sprinklers is based on the total number of sprinklers in the system:
0-300 sprinklers: Minimum of 6 spare sprinklers.
301-1,000 sprinklers: Minimum of 12 spare sprinklers.
1,001-2,000 sprinklers: Minimum of 18 spare sprinklers.
Why 18 Spare Sprinklers are Required:
For a system containing 1,500 sprinklers, the requirement falls within the range of 1,001 to 2,000 sprinklers, mandating 18 spare sprinklers.
Other Options Explained:
Option A (6) and Option B (12): Insufficient for 1,500 sprinklers.
Option D (24): Exceeds the required minimum.
Summary:
A system with 1,500 sprinklers requires a minimum of 18 spare sprinklers.
NEW QUESTION # 104
......
Preparation of professional Certified Fire Inspector I (CFI-1) (CFI-I) exam is no more difficult because experts have introduced the preparatory products. With PassExamDumps products, you can pass the Certified Fire Inspector I (CFI-1) (CFI-I) exam on the first attempt. If you want a promotion or leave your current job, you should consider achieving a professional certification like Certified Fire Inspector I (CFI-1) (CFI-I) exam. You will need to pass the NFPA CFI-I exam to achieve the Certified Fire Inspector I (CFI-1) (CFI-I) certification.